Session of 2026
SENATE BILL No. 400
By Committee on Utilities
1-27
1AN ACT concerning data centers; relating to water consumption; requiring
2data centers to use closed-loop cooling systems to mitigate water
3consumption.
4
5Be it enacted by the Legislature of the State of Kansas:
6Section 1. (a) To conserve and protect Kansas from the on-site water
7consumption footprint that is associated with the operation of large data
8centers, a large load data center shall not utilize an open loop cooling or
9heat removal system that directly exposes or discharges water vapors
10created by such cooling or heat removal processes to the ambient
11atmosphere. A large load data center may use a closed-loop cooling or heat
12removal system that is designed to provide a sealed cooling or heat
13removal system in which no contact is made between any fluid that is
14being cooled or heated and the ambient atmosphere.
15(b) The attorney general, or a city, county or district attorney may
16apply to the district court for a temporary or permanent injunction, or any
17other appropriate legal or equitable remedy, to prohibit any person or
18entity from violating the provisions of this section. Such court shall have
19jurisdiction upon hearing and for cause shown to grant such injunction and
20may make and render such judgments, orders and decrees as may be
21proper to enforce the provisions of this section.
22(c) As used in this section:
23(1) "Data center" means any facility, including any buildings,
24equipment, structures or other stationary items of a facility that are:
25(A) Located on a single premises or on any contiguous and adjacent
26premises;
27(B) used by any person or entity to house computer and network
28systems and infrastructure, including, but not limited to, associated
29components such as servers, network equipment and appliances,
30communications and data storage systems, systems for monitoring and
31managing system and infrastructure performance, data communications
32connections, environmental controls, cooling or heat removal systems, fire
33protection systems and security systems and services; and
34(C) operated with the primary purpose of providing for the storage,
35management, processing and transferring of digital data.
36(2) "Large load data center" means any data center that has or is
1reasonably expected to have a monthly maximum electrical demand of 20
2megawatts or more.
3Sec. 2. This act shall take effect and be in force from and after its
4publication in the statute book.